Add to Favorites   Business post office    Select Language: ENGLISH | 中国

PRODUCT

Your location:Home > Product
Product
MI Electric Heating Cable

SPECIFICATION:
Outputting Constant Wattage
Max Voltage  600V
Max Using Length  3000 m
Max Heat tracing Temperature  590℃
Max Enduring Temperature  700℃
High  Watt Density
One or Two Heating Conductors
Fitting for Explosion-proof area
Enduring strike and high capability Metal Sheath
600V Single Conductor Stainless Steel Sheathed Heating Cable
Cable Type
Conductor
Resistance
Outer Dia.
Max Total
Lentgth
Weight
(Ω/km@20℃)
(mm)
(m)
(kg/km)
 600V Single Conductor
 1H06562SA
6.562
3.7
541
68
 1H05249SA
5.249
4.1
450
83
 1H04265SA
4.265
4.1
450
83
 1H03281SA
3.281
4.1
450
83
 1H02789SA
2.789

4.3

396
83
 1H02297SA
2.297
4.1
450
83
 1H01640SA
1.640
4.6
354
107
 1H01247SA
1.247
3.1
354
107
 1HS00984A
0.984
3.4
354
107
 1H00820SB
0.820
3.3
366
107
 1H00656SB
0.656
3.7
354
107
 1H00558SB
0.558
4.6
354
107
 1H00492SB
0.492
4.6
354
109
 1H00328SB
0.328
5.0
299
131
 1H00262SB
0.262
5.5
250
158
 1H00230SB
0.230
5.0
299
135
 1H00197SB
0.197
4.4
250
162
 1H00131SB
0.131
6.2
192
214
 1H00118SB
0.118
4.8
183
79
 1H00098SB
0.098
6.2
192
223
 1H00066SQ
0.066
5.0
299
131
 1H00052SC
0.052
4.8
183
79
 1H00043SC
0.043
4.8
183
79
 1H00033SL
0.033
4.8
328
115
 1H00021SL
0.021258
5.1
296
129
 1H00013SL
0.013418
5.4
259
151
 1H00008SL
0.008464
6.1
204
195
 1H00005SL
0.005215
6.4
183
226
 1H00003SL
0.003346
7.3
143
298
 1H00002SL
0.00210
8.1
114
388
Record:
1.The tolerance for cable resistance:±5%
2.Recommending the Max Wattage:210W/m
3.Max wattage for tube heat tracing is amended  according to maintain temperature and working temperature.
4.Min bend radius is 5 times nominal cable outer Dia

«1 2 3 4 5 6 7 »

    
ISO9001、Ex、ATEX、FM、EAC、CE、UL、WPQR(Comply With PED、ASME)    
COPYRIGHT © 2016 Wuxi AOK Electrical Equipment Limited ALL RIGHT RESERVED.
Su ICP 05031845-1