Your location:Home > Product
Product
LV self-regulating & low temperature electric heating cable |
SPECIFICATION: |
Self-regulating and save energy |
Rated Voltage 220V/110V |
Max Using Length 170 m |
Max Heat tracing Temperature 65℃ |
the most Suitable Temperature for heat tracing 40℃ |
Outline Size 5.3×12.6 mm Local Cutting at random 10、16、24 W/m(10℃) Min. Bending Radius 30mm |
Fitting for Explosion-proof zone 1、2 | |
|
Temperature group T6 |
A 16AWG Copper Bus Wires |
B Semiconductor heating Core |
C Insaluting Jacket |
D Tinned Copper Braid |
E Overjacket(optional) |
|
Type |
Output Power |
15LV-2SJ |
27.9-0.36Tp |
10LV-2SJ |
18.6-0.24Tp |
5LV-2SJ |
12.7-0.24Tp | Record:Tp is the pipe temperature | |
Heat Output for Heating Cable W/m |
|
Circuit breaker selection (Unit: Meter ) |
Cable Type |
Openning Temp.10℃ |
Openning Temp.-10℃ |
Openning Temp.-30℃ |
10A |
15A |
20A |
25A |
10A |
15A |
20A |
25A |
30A |
10A |
15A |
20A |
25A |
30A |
40A |
5LV-2 |
100 |
150 |
170 |
|
71 |
106 |
142 |
170 |
|
59 |
88 |
118 |
148 |
170 |
|
10LV-2 |
71 |
106 |
142 |
150 |
50 |
75 |
100 |
150 |
|
40 |
60 |
80 |
100 |
120 |
150 |
15LV-2 |
47 |
70 |
94 |
110 |
37 |
56 |
74 |
93 |
110 |
30 |
45 |
60 |
75 |
90 |
110 |
Suggestion: PLS using the thermal magnetic circuit breaker . For it can “nuisance trip” at low temperature. | |
型号含义: |
|
|
|
|